Bard W48L23 Spezifikationen Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 19
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
Manual 2100-594
Page 10 of 19
FIGURE 4
ELECTRIC HEAT CLEARANCE
W48A23, W48L23, W60A23, W60L23
WARNING
A minimum of 1/4 inch clearance must be maintained between
the supply air duct and combustible materials. This is required for
the rst 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible
material and may result in a re causing damage, injury or death.
SIDE SECTION VIEW OF SUPPLY AIR DUCT
FOR WALL MOUNTED UNIT SHOWING 1/4 INCH
CLEARANCE TO COMBUSTIBLE SURFACES.
Seitenansicht 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 18 19

Kommentare zu diesen Handbüchern

Keine Kommentare